NEC Box Fill Calculator

Calculate the minimum required box volume per NEC Article 314.16 based on conductors, devices, and fittings inside the box.

Conductor Size & Volume Allowance Volume per conductor per NEC Table 314.16(B)
Conductor Counts All grounds combined count as ONE conductor (largest ground size used).
Devices & Fittings Each device = 2× the volume allowance of the largest conductor.

One or more internal clamps = 1× volume allowance of largest conductor.

One or more studs/hickeys = 1× volume allowance of largest conductor.

Formula — NEC Article 314.16(B)

Total Fill (in³) = Conductor Fill + Device Fill + Ground Fill + Clamp Fill + Stud Fill

  • Conductor Fill: (Hot count + Neutral count) × Volume per conductor
  • Ground Fill: If any grounds present → 1× Volume per conductor (largest ground)
  • Device Fill: Device count × 2 × Volume per conductor (largest conductor)
  • Clamp Fill: If internal clamps present → 1× Volume per conductor
  • Stud Fill: If fixture studs/hickeys present → 1× Volume per conductor

Volume allowances per NEC Table 314.16(B):
18 AWG=2.0 in³ | 16 AWG=2.25 in³ | 14 AWG=2.5 in³ | 12 AWG=2.75 in³ | 10 AWG=3.0 in³ | 8 AWG=3.5 in³ | 6 AWG=5.0 in³

Assumptions & References

  • Based on NEC 2020 Article 314.16 — Conductors in Outlet, Device, and Junction Boxes.
  • All equipment grounding conductors (regardless of count) are counted as a single conductor using the volume of the largest grounding conductor present.
  • Each single yoke/strap device counts as two conductors at the volume of the largest conductor connected to that device.
  • Conductors that originate and terminate within the box (e.g., pigtails ≤ 6 in) are not counted.
  • Conductors passing through the box without splice or termination each count as one conductor.
  • This calculator assumes all conductors are the same AWG for simplicity. For mixed sizes, calculate each group separately per NEC 314.16(B)(1).
  • Always verify with your local AHJ (Authority Having Jurisdiction) and the adopted NEC edition.